Odyssey

Standard features




























































Voltage regulation IGBT control (double conversion technology)
Voltage stabilisation Independent phase control
Available nominal voltage* 220-230-240V (L-N)
380-400-415V (440-460-480V**) (L-L)
Output voltage accuracy ±0,5%
Frequency 50Hz ±5% or 60Hz ±5%
Correction time <3 millisecs
Admitted load variation Up to 100%
Admitted load imbalance 100%
Cooling Forced ventilation
Ambient temperature -20/+40°C
Storage temperature -25/+60°C
Max relative humidity <95% (non condensing)
Admitted overload 150% for 1 minute (at nominal imput voltage)
Colour RAL 9005
Protection degree IP21
User interface 10″ Touch panel, multilingual (Ethernet communication)
Remotely available by dedicated «client»
Installation Indoor
Communication system MODBUS RTU (RS485)
Overvoltage protection Input class I surge arrestors
Output class II surge arrestors
Protection Automatic by-pass protection

* The output voltage can be adjusted by choosing one of the indicated values.
Such choice sets the new nominal value as a reference for all the stabilizer parameters.

** 60Hz only.

Accessories
  • Interrupting devices
  • Short circuit output protection
  • Manual by-pass line
  • Total protection kit
  • Input isolating transformer
  • Integrated automatic power factor correction system
  • EMI/RFI filters
  • IP54 protection degree for indoor and outdoor installation

The use of the double conversion technology guarantees the insulation from the disturbances and the distortions of the network and, together with the help provided by the electrolytic capacitors, makes it possible to build machines for high power loads.

Odyssey can operate with a load variation range for each phase from 0 to 100%, it is not affected by the power factor of the load and they can work with or without the neutral.

This voltage stabilizer can operate with different input and, consequently, output voltage (380V or 415V) from the nominal one (400V). Such setting can be performed at the factory or at the Customer’s premises according to the instructions given in the handbook. It is also possible to select an output voltage different from the nominal one, but it is necessary to take into account the reduction of the power and the adjustment interval of the machine.

The user interface is created using a multilingual «touch panel» (10″) with an Ethernet communication port which, via dedicated «client», allows remote control. Through the selection menu, it is possible to display electrical values and set the operating parameters of the stabilizer.

It is also possible to communicate with the electronic component via the RS485 serial bus using the Modbus RTU protocol.

The standard cabinet is an IP21 metal enclosure with RAL9005 finish for indoor installation. Cooling is guaranteed by extracting fans.

Read all