Standard features













































Selectable output voltage (dip-switch)* 220-230-240V
Output voltage accuracy ±0,5%
Frequency 50Hz ±5% or 60Hz ±5%
Admitted load variation Up to 100%
Cooling Natural ventilation (aided with fans)
Ambient temperature -25/+45°C
Storage temperature -25/+60°C
Max relative humidity 95% (non condensing)
Admitted overload 200% 2 min.
Harmonic distortion None introduced
Colour RAL 7035
Protection degree IP 21
Instrumentation Output digital voltmetre
Installation Indoor
Overvoltage protection Class II output surge arrestor

* The output voltage can be adjusted by choosing one of the indicated values.
Such choice sets the new nominal value as a reference for all the stabilizer parameters.

Accessories
  • Interrupting devices
  • Load protection against over/undervoltage
  • Manual by-pass line
  • Input isolating transformer
  • SPD surge arrestor
  • EMI/RFI filters
  • IP54 protection degree for indoor and outdoor installation

Antares stabilizers are available for different ranges of input voltage fluctuation.

Standard models offer a double input connection so that with the same unit two different input variations (±1 5%/±20% or ±25%/±30%) can be dealt with.

An automatic circuit breaker is provided on the regulation circuit to protect against overload and short circuit on the voltage regulator whilst the auxiliary circuit is protected by fuses.

The instrumentation consists of a digital multimetre installed on the cabinet front panel. The alarms (min/max output voltage, gearmotor lock, internal overheating, regulator overload) are recognizable by means of LEDs on the control card.

The control logic is based on a digital microprocessor.

All Antares stabilizers are fitted with the same control card, thus simplifying maintenance operations and spare parts storage.